3-pole, front operated, base mounted, DIN-rail mountable switch-diconnector / non-fusible diconnect switch with protected clamp terminals, handle and shaft are not included
Product Net Width:35 mm
Product Net Height:68 mm
Product Net Depth / Length:56 mm
Product Net Weight:0.09 kg
Unit of measurement : Pcs
Technical
Rated Operational Current AC-21A (Ie):(380 ... 415 V) 25 A
(500 V) 25 A
(690 V) 25 A
Rated Operational Current AC-22A (Ie):(380 ... 415 V) 25 A
(500 V) 25 A
(690 V) 25 A
Rated Operational Current AC-23A (Ie):(380 ... 415 V) 20 A
(500 V) 20 A
(690 V) 11 A
Rated Operational Power AC-23A (Pe):(220 ... 240 V) 4 kW
(400 ... 415 V) 9 kW
(500 V) 9 kW
(690 V) 9 kW
Conventional Free-air Thermal Current (Ith):Θ = 40 °C 32 A
Conventional Thermal Current (Ithe):Fully Enclosed 32 A
Rated Impulse Withstand Voltage (Uimp):8 kV
Rated Insulation Voltage (Ui):acc. to IEC/EN 60664-1 750 V
Rated Operational Voltage:Main Circuit 750 V
Rated Short-Circuit Making Capacity (Icm):(690 V) 0.71 kA
Rated Short-time Withstand Current Low Voltage (Icw):for 1 s 0.5 kA
Rated Conditional Short-Circuit Current (Inc):(40 A fuse, ≤415V) 50 kA
(25 A fuse, 690 V) 50 kA
Power Loss:at Rated Operating Conditions per Pole 0.6 W
Pollution Degree:3
Handle Type:Knob
Handle and shaft not included
Switches Operating Mechanism:Mechanism on Top of the Switch
Distance Between Phases:Standard
Position of Line Terminals:Top In - Bottom Out
Bottom In - Top Out
Operating Mode:Front operated
Standards:IEC 60947-3 / UL 508 / CSA C22.2 No. 14
Special Functions:No
Mounting Type:Base mounting
Number of Poles:3
Cable Cross-Section:Cu 0.75 ... 10 mm²
Wire Stripping Length:Main Circuit 9-10 mm
Main Circuit 0.35-0.38 in
Degree of Protection:Front IP20
Terminal Type:Screw Terminals
Tightening Torque:acc. IEC 60947-1 0.8 N·m
Mechanical Durability:20000
Lock Type:No
S$ 61.20
(exc. GST)
S$ 66.71
(inc. GST)
Lead time of 60 working days required.
Item will be ready to dispatch within the lead time specified.