Shopping List
Shopping List
SGD - S$
Image
/
/
/
/
Schneider Electric RMCL55BD Voltage or Current Converter, Harmony Analog, Isolated 0...20mA
Schneider Electric RMCL55BD Voltage or Current Converter, Harmony Analog, Isolated 0...20mA
Image
Image
Product Description

Schneider Electric RMCL55BD Voltage or Current Converter, Harmony Analog, Isolated 0...20mA

This voltage/current converter is part of the range of Harmony Analog. It allows conversion of the most common signals. Its supply voltage is 24V DC, isolated. It features four inputs with voltage/current range of 0V to 10V, +/- 10V, 0mA to 20mA, and 4mA to 20mA. It has four outputs with a switchable voltage/current range of 0V to 10V, +/- 10V, 0mA to 20mA, and 4mA to 20mA. It also allows the connection distance between a sensor and the measurement acquisition device to be increased. It weighs 0.120Kg. Conforming to IEC standards, UL and CSA certified, this converter is suitable for universal use. Quick and intuitive setting, easy to use with fixed input and output values according to the market needs. The settings are secure with sealable protective cover.

Main

  • Range of Product: Harmony Analog
  • Product or Component Type: Voltage/Current Converter
  • Analogue Input Type:
    • Current: 0...20 mA
    • Current: 4...20 mA
    • Voltage: +/- 10 V DC
    • Voltage: 0...10 V DC
  • Analogue Output Type:
    • Current: 0...20 mA (≤ 500 Ohm, Switchable)
    • Current: 4...20 mA (≤ 500 Ohm, Switchable)
    • Voltage: +/- 10 V (≥ 100 kOhm, Switchable)
    • Voltage: 0...10 V (≥ 100 kOhm, Switchable)

Complementary

  • Protection Type:
    • Reverse Polarity Protection on Output
    • Short-Circuit Protection on Output
    • Overvoltage Protection on Output (+/- 30 V)
    • Abnormal Analogue Output Voltage:
      • 11...15 V, Output Selected: -10...10 V (No Input or Input Wire Broken Voltage)
      • 11...15 V, Output Selected: 0...10 V (No Input or Input Wire Broken Voltage)
      • -15...0 V, Output Selected: 0...20 mA (No Input or Input Wire Broken Current)
      • -15...0 V, Output Selected: 4...20 mA (No Input or Input Wire Broken Current)
    • Abnormal Analogue Output Current:
      • 22…30 mA, Output Selected: 0...20 mA (No Input or Input Wire Broken Voltage)
      • 22…30 mA, Output Selected: 4...20 mA (No Input or Input Wire Broken Voltage)
      • -30…0 mA, Output Selected: 0...20 mA (No Input or Input Wire Broken Current)
      • 4…30 mA, Output Selected: 4...20 mA (No Input or Input Wire Broken Current)
  • Rated Supply Voltage [Us]: 24 V DC +/- 20 %, Isolated
  • Current Consumption:
    • <= 70 mA for Voltage Output
    • <= 90 mA for Current Output
  • Local Signalling: LED (Green) for Power ON
  • Measurement Error: +/- 5 % of Full Scale at 20 °C (Temporary Performance Degradation when Subject to Electromagnetic Interference)
  • Repeat Accuracy:
    • +/- 0.2 % Full Scale at 20 °C
    • +/- 0.6 % Full Scale at 60 °C
  • Temperature Coefficient: 200 ppm/°C
  • Clamping Connection Capacity:
    • 2 x 1.5 mm²
    • 1 x 2.5 mm²
  • Tightening Torque: 0.6…1.1 N.m
  • Marking: CE
  • Surge Withstand: 0.5 kV during 1.2/50 µs conforming to IEC 61000-4-5
  • Rated Insulation Voltage [Ui]: 2 kV
  • Fixing Mode:
    • By Screws (Mounting Plate)
    • Clip-on (35 mm Symmetrical DIN Rail)
  • Safety Reliability Data:
    • B10d = 20000
    • MTTFd = 21.6 years
  • Net Weight: 0.12 kg

S$ 489.00
(exc. GST)
S$ 533.01
(inc. GST)
Quantity:
EA
This item is sold by
Image
Schneider Electric
0
Highly Matched Items
View items that have the same or are a close match to the specifications of this item
Signal Conditioners from SCHNEIDER ELECTRIC
Source & compare similar products
More from Signal Conditioners
Expand your search with a wider selection
Recently Viewed Products
Compare & Refer to previously viewed items
Image
Top